Heat pump won't cool, condenser outside clicking and won't run


Not a lot of pictures here because i didn't think this fix would be the epic that it was.
The system is a generic International Comfort Products.   Inside the box I found that Trane, Tempstar, Heil and ICP units use a lot of the same parts.  So pretty much ignore the brand name on the unit.

First hot day in a while and the wife switches the heat pump to cooling mode and when I get home she complains it is not cooling.

Quick inspection reveals warm air blowing and the outside unit - condenser - is not running when the thermostat says it is cooling.   The strangest thing is the condenser outside is quiet except for a fairly loud clicking about once every 2-3 seconds.

The solution was that the solenoid for the reversing valve (inside the outside condenser) was bad.  It was shorted out.   Replacing it is easy and can be done by opening the unit and removing one nut and plugging in the wires.  Cost was less than $15 and can be done with only a socket wrench.


Here is how i figured it out...  I bit of a comedy of errors but I got there in the end.

Google searching doesn't help. So i decide to start swapping parts.

I open the access panel on the outside of the condenser.   With my finger feeling i discover that one of the relays on the control board is doing the clicking.   My voltmeter shows the unit is getting both 240V and 24V power.   The contactor (big relay) coil is not powered, so something is not telling the unit to start.

I decided the control board might be broken and ordered one on ebay for $20.
Heil Tempstar Defrost Control Board 1087952 CEPL130547-01 CEBD430547-02A
http://www.ebay.com/itm/232274455696?_trksid=p2060353.m2749.l2649&ssPageName=STRK%3AMEBIDX%3AIT



Picture of the contactor on the left, and the control board on the right.


When the control board came a few days later i swapped it in.  all the connections are pull off and plug back in.  just transfer the wires one by one.

All done, i go to turn it on and I find the thermostat is BLANK.   Measuring the voltage at the green/red thermostat wires after pulling off the thermostat from the wall, i find i have no 24V anymore.   At the condenser no 24V either.   Whaaa?  It was there before.  I either blew the transformer or something else did in the 4 days since I tested before.   

Upstairs in the attic I open the panel on the air handler.  The transformer is in the back in the lower right.  No 24V on it's output.  Remove it and find that the primary coil measures open. 



I buy one on ebay for $11.99



Comfortmaker Heil Tempstar 24v Repacement Relay Contactor 1050699 HQ1050699HW


http://www.ebay.com/itm/222179588108?_trksid=p2060353.m2749.l2649&ssPageName=STRK%3AMEBIDX%3AIT


When transformer comes I swap it in.  Now I have 24V power.  Thermostat is working again.   Outside the condenser is clicking again.  A week with out cooling and a total fail.  I'm right where I started.   It was not the control board.

At this point I got lucky.  I played with the thermostat and I find that the unit will heat, but not cool.  In heat mode the condenser starts right up and heat pours out.  That is the big clue.  Googling heat and no cool problem I find quickly that the reversing valve is likely the issue.   The reversing valve switches the direction of flow of coolant.

Reversing valve is inside the the outside unit.  I have to take the top off with the fan and reach down.   The reversing valve looks like this. I didn't take a real picture, this is generic picture.   On top is the solenoid.   When I disconnected the wires from it, the clicking stopped.
I measured the voltage at the solenoid and it was getting 24V.   There was no magnetic field from the soldenoid (put a screwdriver near it and it should be attracted) and resistance was about 1.5 ohms.  It should be 10-60 ohms.   The solenoid part (blue in this picture, but red in my unit) comes right out by removing the nut you see on the side.

I ordered a new one for $12.75.  
Trane American Standard Heat Pump Reversing Valve Solenoid Coil COL05901

When new solenoid came I swapped it in and everything worked! It took nearly two weeks waiting for three parts in a row but at least i saved a lot of money despite my bumbling.

After thinking about this repair I think the 24V transformer was the root cause of blowing the reversing valve solenoid.   The PRIMARY of the transformer was open when it was blown, which makes no sense that I blew it swapping parts.  Perhaps the 24V over voltaged the solenoid and blew it.   So that makes me feel better, i replaced the bad transformer in the process.



31 comments:

  1. thanks for sharing.for more information : click here

    ReplyDelete
  2. Thanks for sharing your experience. Puzl

    ReplyDelete
  3. They have a competent team of expert freelance writers who have vast experience in all areas such as commercial, social and academic. Academic Writing Services

    ReplyDelete
  4. There are online courses available on the internet which teaches whole data science technology through video tutorials and theory as well. There would be assignments which you have to complete. 360DIgiTMG data science institute in hyderabad

    ReplyDelete
  5. It is important for midwifery assignment writing service seekers to find the best Midwifery Writing Services from a reputable midwifery research paper help provider for their custom midwifery essay writing services.

    ReplyDelete
  6. I've read this post and if I could I desire to suggest you some interesting things or suggestions. Perhaps you could write next articles referring to this article. I want to read more things about it!
    data science training in Hyderabad

    ReplyDelete
  7. Thanks for posting the best information and the blog is very informative.Data science course in Faridabad

    ReplyDelete
  8. I want to leave a little comment to support and wish you the best of luck.we wish you the best of luck in all your blogging enedevors.
    data analytics course in bangalore

    ReplyDelete
  9. Really wonderful blog completely enjoyed reading and learning to gain the vast knowledge. Eventually, this blog helps in developing certain skills which in turn helpful in implementing those skills. Thanking the blogger for delivering such a beautiful content and keep posting the contents in upcoming days.

    data science training institute in bangalore

    ReplyDelete
  10. This comment has been removed by the author.

    ReplyDelete
  11. Thanks for posting the best information and the blog is very important.data science institutes in hyderabad

    ReplyDelete
  12. Thanks for posting the best information and the blog is very important.digital marketing institute in hyderabad

    ReplyDelete
  13. Thanks for posting the best information and the blog is very important.data science institutes in hyderabad

    ReplyDelete
  14. Tremendous blog quite easy to grasp the subject since the content is very simple to understand. Obviously, this helps the participants to engage themselves in to the subject without much difficulty. Hope you further educate the readers in the same manner and keep sharing the content as always you do.

    data science course in faridabad

    ReplyDelete
  15. Nice to be visiting your blog once more, it has been months for me. Well this article that ive been waited for therefore long. i want this article to finish my assignment within the faculty, and it has same topic together with your article. Thanks, nice share.
    data scientist course in hyderabad

    ReplyDelete
  16. Thanks for posting the best information and the blog is very good.data science course in Lucknow

    ReplyDelete
  17. I was just examining through the web looking for certain information and ran over your blog.It shows how well you understand this subject. Bookmarked this page, will return for extra. data science course in vadodara

    ReplyDelete
  18. Thanks for sharing this blog with us. Keep sharing more stuff with us.
    AI Patasala Data Science Course in Hyderabad

    ReplyDelete
  19. Thank you quite much for discussing this type of helpful informative article. Will certainly stored and reevaluate your Website.
    Data Analytics Course in Bangalore

    ReplyDelete
  20. Amazingly by and large very interesting post. I was looking for such an information and thoroughly enjoyed examining this one. Keep posting. An obligation of appreciation is all together for sharing.data analytics course in rohtak

    ReplyDelete
  21. Easily, the article is actually the best topic on this registry related issue. I fit in with your conclusions and will eagerly look forward to your next updates. business analytics course in surat

    ReplyDelete
  22. It's late finding this act. At least, it's a thing to be familiar with that there are such events exist. I agree with your Blog and I will be back to inspect it more in the future so please keep up your act. business analytics course in surat

    ReplyDelete
  23. 360DigiTMG, the top-rated organisation among the most prestigious industries around the world, is an educational destination for those looking to pursue their dreams around the globe. The company is changing careers of many people through constant improvement, 360DigiTMG provides an outstanding learning experience and distinguishes itself from the pack. 360DigiTMG is a prominent global presence by offering world-class training. Its main office is in India and subsidiaries across Malaysia, USA, East Asia, Australia, Uk, Netherlands, and the Middle East.

    ReplyDelete
  24. With so many books and articles coming up to give gateway to make-money-online field and confusing reader even more on the actual way of earning money, data science training in kanpur

    ReplyDelete
  25. Nice thanks for sharing informative post like this keep posting if like more details visit my website linkhttps://snowflakemasters.in/

    ReplyDelete