Not a lot of pictures here because i didn't think this fix would be the epic that it was.
The system is a generic International Comfort Products. Inside the box I found that Trane, Tempstar, Heil and ICP units use a lot of the same parts. So pretty much ignore the brand name on the unit.
First hot day in a while and the wife switches the heat pump to cooling mode and when I get home she complains it is not cooling.
Quick inspection reveals warm air blowing and the outside unit - condenser - is not running when the thermostat says it is cooling. The strangest thing is the condenser outside is quiet except for a fairly loud clicking about once every 2-3 seconds.
The solution was that the solenoid for the reversing valve (inside the outside condenser) was bad. It was shorted out. Replacing it is easy and can be done by opening the unit and removing one nut and plugging in the wires. Cost was less than $15 and can be done with only a socket wrench.
Here is how i figured it out... I bit of a comedy of errors but I got there in the end.
Google searching doesn't help. So i decide to start swapping parts.
I open the access panel on the outside of the condenser. With my finger feeling i discover that one of the relays on the control board is doing the clicking. My voltmeter shows the unit is getting both 240V and 24V power. The contactor (big relay) coil is not powered, so something is not telling the unit to start.
I decided the control board might be broken and ordered one on ebay for $20.
Heil Tempstar Defrost Control Board 1087952 CEPL130547-01 CEBD430547-02A
http://www.ebay.com/itm/232274455696?_trksid=p2060353.m2749.l2649&ssPageName=STRK%3AMEBIDX%3AIT
Picture of the contactor on the left, and the control board on the right.
When the control board came a few days later i swapped it in. all the connections are pull off and plug back in. just transfer the wires one by one.
All done, i go to turn it on and I find the thermostat is BLANK. Measuring the voltage at the green/red thermostat wires after pulling off the thermostat from the wall, i find i have no 24V anymore. At the condenser no 24V either. Whaaa? It was there before. I either blew the transformer or something else did in the 4 days since I tested before.
Upstairs in the attic I open the panel on the air handler. The transformer is in the back in the lower right. No 24V on it's output. Remove it and find that the primary coil measures open.
I buy one on ebay for $11.99
Comfortmaker Heil Tempstar 24v Repacement Relay Contactor 1050699 HQ1050699HW
When transformer comes I swap it in. Now I have 24V power. Thermostat is working again. Outside the condenser is clicking again. A week with out cooling and a total fail. I'm right where I started. It was not the control board.
At this point I got lucky. I played with the thermostat and I find that the unit will heat, but not cool. In heat mode the condenser starts right up and heat pours out. That is the big clue. Googling heat and no cool problem I find quickly that the reversing valve is likely the issue. The reversing valve switches the direction of flow of coolant.
Reversing valve is inside the the outside unit. I have to take the top off with the fan and reach down. The reversing valve looks like this. I didn't take a real picture, this is generic picture. On top is the solenoid. When I disconnected the wires from it, the clicking stopped.
I measured the voltage at the solenoid and it was getting 24V. There was no magnetic field from the soldenoid (put a screwdriver near it and it should be attracted) and resistance was about 1.5 ohms. It should be 10-60 ohms. The solenoid part (blue in this picture, but red in my unit) comes right out by removing the nut you see on the side.
I ordered a new one for $12.75.
Trane American Standard Heat Pump Reversing Valve Solenoid Coil COL05901
After thinking about this repair I think the 24V transformer was the root cause of blowing the reversing valve solenoid. The PRIMARY of the transformer was open when it was blown, which makes no sense that I blew it swapping parts. Perhaps the 24V over voltaged the solenoid and blew it. So that makes me feel better, i replaced the bad transformer in the process.
thanks for sharing.for more information : click here
ReplyDeleteThank you for bringing that experience to you. I like this post very much. clash royale hungry shark evolution game download download my talking angela mod apk
ReplyDeleteThanks for sharing your experience. Puzl
ReplyDeleteThey have a competent team of expert freelance writers who have vast experience in all areas such as commercial, social and academic. Academic Writing Services
ReplyDeleteQuite right! It is good idea. It is ready to support you. https://royalcbd.com/product/cbd-oil-500mg/
ReplyDeleteThere are online courses available on the internet which teaches whole data science technology through video tutorials and theory as well. There would be assignments which you have to complete. 360DIgiTMG data science institute in hyderabad
ReplyDeleteThis comment has been removed by the author.
ReplyDeleteThanks for sharing this blog with us. Keep sharing more stuff with us.
ReplyDeleteAI Patasala Data Science Course in Hyderabad
360DigiTMG, the top-rated organisation among the most prestigious industries around the world, is an educational destination for those looking to pursue their dreams around the globe. The company is changing careers of many people through constant improvement, 360DigiTMG provides an outstanding learning experience and distinguishes itself from the pack. 360DigiTMG is a prominent global presence by offering world-class training. Its main office is in India and subsidiaries across Malaysia, USA, East Asia, Australia, Uk, Netherlands, and the Middle East.
ReplyDelete